Power Factor Correction Calculator

Capacitor kvar and µF needed to raise the power factor of a load.

Electrical & Electronic

Loading calculator…

Capacitors supply the reactive power that motors draw, which lowers the current from the grid and can cut demand charges.

How to use this calculator

  1. Enter the real power and the present and target power factors.
  2. Enter the voltage, frequency and phases (and the capacitor connection for three-phase).
  3. Read the kvar and the capacitance per phase.

Formula

Qc = P × (tan φ1 − tan φ2), C = Qc / (2πf × V²)

Worked example

50 kW at PF 0.75 raised to 0.95: Qc = 50 × (0.882 − 0.329) = 27.7 kvar.

Frequently asked questions

Why not correct to exactly 1.0?

Over-correction makes the load capacitive and can cause over-voltage and resonance. Targets of 0.95–0.98 are common.

Delta or star capacitors?

Delta-connected capacitors need one third of the capacitance of star-connected ones for the same kvar.