Three-Phase Power Calculator

kW, kVA and kvar from line voltage, current and power factor — or the current for a load.

Electrical & ElectronicMechanical

Loading calculator…

In a balanced three-phase system the power is √3 times line voltage times line current. The power factor splits it into real (kW) and reactive (kvar) parts.

How to use this calculator

  1. Choose whether you know the current or the power.
  2. Enter the line-to-line voltage (400 V, 415 V, 480 V…) and the power factor.
  3. Add the motor efficiency to see the shaft output.

Formula

S = √3 × VL × IL, P = S × PF, Q = S × sin(acos PF)

Worked example

400 V, 32 A, PF 0.85: S = 22.2 kVA, P = 18.8 kW, Q = 11.7 kvar.

Frequently asked questions

Line or phase voltage?

Use the line-to-line voltage (between two phases). That is the value on most nameplates.

What power factor should I use for a motor?

Use the nameplate value; at full load it is usually 0.8–0.9, and lower at part load.

Results are for learning and preliminary design. Check critical work against the relevant codes and a qualified engineer.