In a balanced three-phase system the power is √3 times line voltage times line current. The power factor splits it into real (kW) and reactive (kvar) parts.
How to use this calculator
- Choose whether you know the current or the power.
- Enter the line-to-line voltage (400 V, 415 V, 480 V…) and the power factor.
- Add the motor efficiency to see the shaft output.
Formula
S = √3 × VL × IL, P = S × PF, Q = S × sin(acos PF)Worked example
400 V, 32 A, PF 0.85: S = 22.2 kVA, P = 18.8 kW, Q = 11.7 kvar.
Frequently asked questions
Line or phase voltage?
Use the line-to-line voltage (between two phases). That is the value on most nameplates.
What power factor should I use for a motor?
Use the nameplate value; at full load it is usually 0.8–0.9, and lower at part load.
Results are for learning and preliminary design. Check critical work against the relevant codes and a qualified engineer.