Long or thin cables lose voltage. This calculator uses the conductor resistance at its operating temperature to find the drop for DC, single-phase and three-phase circuits.
How to use this calculator
- Pick the system and conductor material.
- Enter the one-way cable length, the current and the conductor size.
- Enter the supply voltage to see the drop in percent. Use 70 °C for PVC cable at full load.
Formula
ΔV = k × L × I × ρ(T) / A, k = 2 (single-phase/DC) or √3 (three-phase)Resistance only — reactance is ignored, which is accurate for cables up to about 25 mm². Always check your local wiring code.
Worked example
25 m of 2.5 mm² copper carrying 16 A on 230 V at 20 °C: ΔV ≈ 5.5 V (2.4 %).
Frequently asked questions
What voltage drop is acceptable?
Many codes recommend about 3 % for a final circuit and 5 % in total from the supply to the load.
Why does temperature matter?
Copper resistance rises about 0.39 % per °C, so a cable at 70 °C has about 20 % more resistance than at 20 °C.
Results are for learning and preliminary design. Check critical work against the relevant codes and a qualified engineer.