An ideal transformer scales voltage by its turns ratio and current by the inverse. Full-load current follows from the kVA rating.
How to use this calculator
- Choose single or three-phase.
- Enter the primary and secondary voltages.
- Add the kVA rating for currents and the primary turns for the secondary turns.
Formula
Vp/Vs = Np/Ns = Is/Ip, I = S/V (1-phase) or S/(√3 V) (3-phase)Worked example
A 1000 kVA, 11 kV / 415 V three-phase transformer: Ip = 52.5 A, Is = 1391 A, ratio 26.5 : 1.
Frequently asked questions
Does this include losses?
No — it is an ideal transformer. Real units are typically 97–99 % efficient and the secondary voltage sags a few percent at full load.
Line or phase voltage for three-phase?
Use line-to-line voltages, as printed on the nameplate.
Results are for learning and preliminary design. Check critical work against the relevant codes and a qualified engineer.