Transformer Calculator

Turns ratio, secondary turns and full-load currents of a transformer.

Electrical & Electronic

Loading calculator…

An ideal transformer scales voltage by its turns ratio and current by the inverse. Full-load current follows from the kVA rating.

How to use this calculator

  1. Choose single or three-phase.
  2. Enter the primary and secondary voltages.
  3. Add the kVA rating for currents and the primary turns for the secondary turns.

Formula

Vp/Vs = Np/Ns = Is/Ip, I = S/V (1-phase) or S/(√3 V) (3-phase)

Worked example

A 1000 kVA, 11 kV / 415 V three-phase transformer: Ip = 52.5 A, Is = 1391 A, ratio 26.5 : 1.

Frequently asked questions

Does this include losses?

No — it is an ideal transformer. Real units are typically 97–99 % efficient and the secondary voltage sags a few percent at full load.

Line or phase voltage for three-phase?

Use line-to-line voltages, as printed on the nameplate.

Results are for learning and preliminary design. Check critical work against the relevant codes and a qualified engineer.